Warning Output Function - Mitsubishi Electric MELSEC iQ-F FX5 User Manual

Programmable controllers
Hide thumbs Also See for MELSEC iQ-F FX5:
Table of Contents

Advertisement

Warning Output Function

When the digital operation value to which the shift amount is added is above the warning output upper limit value or below the
warning output lower limit value, warning is output.
Digital value
Digital operation value
8000
Warning output
6000
upper limit value
4000
Warning output
2000
lower limit value
ON
Warning output
upper limit value flag
OFF
ON
Warning output
lower limit value flag
OFF
ON
Alarm clear request
OFF
2000 or more
Digital value
2000 or more to
Digital operation value
6000 or less
1.25 V or more to
Analog output value
3.75 V or less
D/A conversion latest
0
alarm code
*1 Analog values below the warning output lower limit value are not output.
*2 Analog values above the warning output upper limit value are not output.
Operation
When the digital operation value to which the shift amount is added is above the warning output upper limit value or below the
warning output lower limit value and the warning output condition is satisfied, the "warning output upper flag" or "warning
output lower flag" turns ON.
When warning is output, the setting value of the "warning output upper limit value/warning output lower limit value" is regarded
as the digital operation value and D/A-converted.
Even if the digital value changes to a value below the warning output upper limit value and above the warning output lower
limit value after the warning output, the "warning output upper flag" and "warning output lower flag" do not turn OFF. When the
alarm clear request is set to OFF, ON and OFF again, the "warning output upper flag" and "warning output lower flag" turn
OFF. The "warning output upper flag" and "warning output lower flag" turn OFF also when the "warning output enable/disable
setting" is changed to "disable", but the alarm code stored in the "D/A conversion latest alarm code" is not cleared.
For clearing the alarm code stored in the "D/A conversion latest alarm code", set the alarm clear request to OFF, ON and OFF
again.
Setting procedure
1.
Set "Warning Output Function" to "Enable".
Navigation window  [Parameter]  [Module Information]  Module model name  [Module Parameter]  "Application
Settings"  "Warning Output Function"
2.
Set values for "Warning output upper limit value" and "Warning output lower limit value".
Item
Warning output upper limit value
Warning output lower limit value
*1
2000 or less
2000 or more to 6000 or less
2000
2000 or more to 6000 or less
1.25 V
1.25 V or more to 3.75 V or less
081
H
*2
6000 or more
6000
3.75 V
080
H
0
Setting range
-32768 to +32767
Digital value
Digital operation value
Excluded
Sampling
2000 or more to
6000 or less
2000 or more to
6000 or less
1.25 V or more to
3.75 V or less
0
3 FX5-4DA-ADP
3.3 Functions
3
107