Application settings
Setting procedure
Open "Application Settings" of the GX Works3.
1.
Start Module parameter.
Navigation window [Parameter] [Module Information] Module model name [Module Parameter] "Application
Settings"
Window
Displayed items
Item
Warning Output Setting
Warning output upper limit value
Warning output lower limit value
Scaling Enable/Disable
Scaling Upper Limit Value
Scaling Lower Limit Value
Shifting amount to conversion
value
HOLD/CLEAR Setting
HOLD Setting Value
Disconnection detection enable/
disable setting
Disconnection recovery detection
enable/disable setting
2.
Click the item to be changed to enter the setting value.
• Item where a value is selected from the pull-down list
Click [] button of the item to be set, and from the pull-down list that appears, select the value.
• Item where a value is entered into the text box
3 FX5-4DA-ADP
122
3.6 Parameter Setting
Description
Set whether to "enable" or "disable" warning output.
Set upper limit value of digital input value for warning output.
Set lower limit value of digital input value for warning output.
Set whether to "enable" or "disable" scaling.
Set scaling conversion upper limit value.
Set scaling conversion lower limit value.
Set shifting amount for shift function.
Set output status at CLEAR or HOLD.
Set digital value that output at HOLD for each channel when
"setting value" is selected in "HOLD/CLEAR setting".
Set whether to "enable" or "disable" disconnection detection.
Set whether to "enable" or "disable" disconnection recovery
detection.
Setting range
• Disable
• Enable
-32767 to +32767
-32768 to +32766
• Disable
• Enable
-32768 to +32767
-32768 to +32767
-32768 to +32767
• CLEAR
• Current Value (Hold)
• Setting Value
-32768 to +32767
• Disable
• Enable
• Disable
• Enable
Default
Disable
Disable
0
Current Value
(Hold)
Disable
Disable