Application setting (Analog output)

Setting procedure
Open "Application settings" of the GX Works3.
1.
Start Module parameter.
Navigation window  [Parameter]  [FX5UCPU]  [Module Parameter]  [Analog Output]  "Application settings"
Window
Displayed items
Item
Warning Output Setting
Warning Upper Limit value
Warning Lower Limit value
Scaling Enable/Disable
Scaling Upper Limit Value
Scaling Lower Limit Value
Shift Value to Conversion Value
HOLD/CLEAR Setting
HOLD Setting Value
2.
Click the item to be changed to enter the setting value.
• Item where a value is selected from the pull-down list
Click [] button of the item to be set, and from the pull-down list that appears, select the value.
• Item where a value is entered into the text box
Description
Set whether to "enable" or "disable" warning output.
Set upper limit value of digital input value for warning output.
Set lower limit value of digital input value for warning output.
Set whether to "enable" or "disable" scaling.
Set scaling conversion upper limit value.
Set scaling conversion lower limit value.
Set shifting amount for shifting function.
Set output status at CLEAR or HOLD.
Set digital value that output at HOLD when "setting value" is
selected in "HOLD/CLEAR Setting".
Setting range
• Enable
• Disable
-32768 to +32767
-32768 to +32767
• Enable
• Disable
-32768 to +32767
-32768 to +32767
-32768 to +32767
• CLEAR
• Previous Value (Hold)
• Setting Value
-32768 to +32767
4 FX5U CPU MODULE BUILT-IN ANALOG
4.7 Parameter Setting
4
Default
Disable
0
0
Disable
0
0
0
CLEAR
0
167