hit counter script

Mitsubishi Electric FX3G SERIES Programming Manual page 163

Programmable controllers
Hide thumbs Also See for FX3G SERIES:
Table of Contents

Advertisement

FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
Cautions
1)
When even if a numeric value written to index registers does not exceed the 16-bit numeric value range (0 to
32767), make sure to overwrite both V and Z using a 32-bit instruction. If only Z is overwritten and another
numeric value remains in V, the numeric value will be extremely large. Thus an operation error occurs.
2)
It is not permitted to use 16-bit counters as 32-bit counters by executing indexing.
When 32-bit counters are required, add Z0 to Z7 to counters C200 and later.
3)
It is not permitted to index V and Z themselves.
4)
Direct specification of buffer memory in special function blocks/units
In the direct specification of buffer memory "U \G ", the buffer memory number can be indexed with index
registers.
The unit number cannot be indexed with index registers.
("U0\G0Z0" is valid, but "U0Z0\G0" is invalid.)
5)
Indexing in bit digit specification
It is not permitted to index "n" in "Kn" used for digit specification.
("K4M0Z0" is valid, but "K0Z0M0" is invalid.)
6)
Indexing of I/O relays (octal device numbers)
When octal device numbers of X, Y, KnX, and KnY are indexed with
index register, the contents of an index register are converted into
octal, and then added to the device number.
In the example shown in the figure on the right, Y007 to Y000 are
output by MOV instruction, and inputs are switched by indexing X007
to X000, X017 to X010, and X027 to X020.
When rewriting the index value as "K0", "K8", "K16", the device
number converted into octal is added "X000 + 0 = X000", "X000 + 8 =
X10", "X000 + 16 = X20", and the input terminal working as the
source is changed accordingly.
Display example of timer present value
A sequence to display the present value of the timers T0 to T9 can be
programmed index registers.
M8000
RUN monitor
"T0Z0 = T0 to T9" according to "Z0 = 0 to 9"
In the case of constants
The indexing operation is explained in an example in which the transfer
destination in MOV instruction is indexed with the index register V6 (as
shown in the figure on the right).
Transfer K0 or K20 to the index register V6 in advance.
When X005 is set to ON, "K(6+0) = K6" if V6 is "0", and K6 is transferred
to D10.
When X005 is set to ON, "K(6+20) = K26" if V6 is "20", and K26 is
transferred to D10.
FNC 19
K1X000
Z0
BIN
(X003 to X000)BCD→(Z0)BIN
FNC 18
T 0Z0
K4Y000
BCD
(T0Z0)BIN→(Y017 to Y000)BCD
5 How to Specify Devices and Constants to Instructions
X030
FNC 12
MOVP
X031
FNC 12
MOVP
X032
FNC 12
MOVP
X033
FNC 12
MOV
: X7 to X0 → Y7 to Y0
V3=0
: X17 to X10 → Y7 to Y0
V3=8
V3=16 : X27 to X20 → Y7 to Y0
Digital switch input
5
for setting timer
number X003 to X000
PLC
Seven-segment display unit
output for displaying
timer current value
Y017 to Y000
X004
FNC 12
MOVP
X004
FNC 12
MOVP
X005
FNC 12
MOVP
V6=0 : K6 (K6+0) → D10
V6=20 : K26(K6+20) → D10
5.7 Indexing
1
2
3
K 0
V 3
4
K 0 → V 3
K 8
V 3
K 8 → V 3
K 16
V 3
5
K16 → V 3
K2X0V3
K2Y0
6
7
8
9
K0
V6
K0 → V6
K20
V6
K20 → V6
10
K6V6
D10
161

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fx3u seriesFx3uc series

Table of Contents