FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
Related devices
1. Instruction execution complete flag
Device
Instruction execution com-
M8029
2. Monitoring the number of generated pulses
The number of pulses output from Y000 or Y001 is stored in the following special data registers:
Device
High
Low
order
order
D8141
D8140
D8143
D8142
D8137
D8136
The contents of each data register can be cleared using the following program:
Command
input
FNC 12
DMOV
3. How to stop the pulse output
• When the command input is set to OFF, the pulse generation is immediately stopped. When the command input is
set to ON again, pulse generation operation restarts from the beginning.
• When the special auxiliary relays (M) shown below are set to ON, the pulse output is stopped.
Device
FX
3G
M8145,M8349
M8146,M8359
To restart pulse output pulses again, set the device (FX
FX
/FX
: M8349, M8359) corresponding to the output signal to OFF, and then drive the pulse output instruction
3U
3UC
again.
Cautions
1. Frequency
S
1
When using transistor outputs on the main unit, set the output frequency
If the load is operated using pulses at a frequency higher than 100,000 Hz from transistor outputs in the main unit, the
PLC may be damaged.
2. Pulse output
• Only a transistor output on the main unit or Y000 or Y001 on a special high-speed output adapter*1 can be
specified in
D
*1.
High-speed output special adapters can be connected only to FX
When using the PLSR (FNC 59) instruction with a relay output type or triac output type FX
high-speed output adapter is required.
• The duration of the ON/OFF pulses is 50% (ON = 50%, OFF = 50%).
• The pulse output is controlled by the dedicated hardware not affected by the sequence program (operation cycle).
• If the command input is set to OFF during continuous pulse output, the output from
Name
OFF: The input command is OFF, or pulses are being output. (This flag does not turn ON if the
pulse output is interrupted in the middle of output.)
plete
ON: Output of the number of pulses set in
Description
Accumulated number of pulses
output from Y000
Accumulated number of pulses
output from Y001
Total accumulated number of
pulses output from Y000 and Y001
Low-order device shown in
K0
above table
FX
•FX
3U
3UC
M8349
Immediately stops pulse output from Y000.
M8359
Immediately stops pulse output from Y001.
.
13 High-Speed Processing – FNC 50 to FNC 59
13.10 FNC 59 – PLSR / Acceleration/Deceleration Setup
→ For the instruction execution complete flag use method,
Description
S
is completed.
2
Contents of data
Accumulated number of pulses output from Y000 by PLSY and PLSR
instructions
Accumulated number of pulses output from Y001 by PLSY and PLSR
instructions
Total accumulated number of pulses output from Y000 and Y001 by PLSY and
PLSR instructions
Description
: M8145, M8146, M8349, M8359
3G
S
1
PLC.
3U
refer to Subsection 6.5.2.
to "100,000 Hz" or less.
PLC, a special
3U
D
turns OFF.
11
12
13
14
15
16
17
18
19
20
385