Number and name
Advanced Function
*1
SWAP function of XCH (FNC 17)
M 8160
*1*2
8-bit process mode
M 8161
M 8162
High-speed parallel link mode
[M]8163
Not used
FROM (FNC 78), TO (FNC 79) instructions:
*1
M 8164
Transfer points variable mode
SORT2 (FNC149) instruction:
*1
M 8165
Sorting in descending order
[M]8166
Not used
HKY (FNC 71) instruction:
*1
M 8167
HEX data handling function
SMOV (FNC 13) instruction:
*1
M 8168
HEX data handling function
[M]8169
Not used
*1.
Cleared when the PLC switches from RUN to STOP.
*2.
Applicable to ASC (FNC 76), RS (FNC 80), ASCI (FNC 82), HEX (FNC 83), CCD (FNC 84), and CRC
(FNC188) instructions
*3.
Available in Ver. 2.00 or later.
*4.
Available in Ver. 2.20 or later.
*5.
CRC (FNC188) instruction is available only in FX
Pulse Catch (Refer to Section 36.7 for details.)
*6
Input X000 pulse catch
M 8170
*6
Input X001 pulse catch
M 8171
*6
Input X002 pulse catch
M 8172
*6
Input X003 pulse catch
M 8173
*6
Input X004 pulse catch
M 8174
*6
Input X005 pulse catch
M 8175
*6
Input X006 pulse catch
M 8176
*6
Input X007 pulse catch
M 8177
*6.
Cleared when PLC switches from STOP to RUN.
FX
, FX
2N
FX
, FX
3G
Communication Port Channel Setting (Refer to Data Communication Edition for details.)
M 8178
Parallel link channel switch (OFF: ch1/ON: ch2)
M 8179
N:N network channel switch
*7.
The channel is specified by either setting or not setting M8179 in the setting program.
• ch1: M8179 is not set in program
• ch2: M8179 is set in program
830
Operation and function
*5
.
, FX
or FX
Series PLC: EI (FNC 04) instruction is necessary.
2NC
3U,
3UC
, FX
, or FX
Series PLC: EI (FNC 04) instruction is unnecessary.
1S
1N
1NC
*7
37 Operation of Special Devices (M8000 -, D8000 -)
37.1 Special Device List (M8000 -, D8000 -)
FX
FX
FX
3G
3U
3UC
*4
and FX
PLCs.
3U
3UC
→ For setting program, Refer to Data Communication Edition
Applicable model
Correspond-
ing special
FX
FX
FX
1S
1N
2N
device
*3
D8164
FX
FX
1NC
2NC

Advertisement