FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
• FX
PLCs (Extention mode)
3G
Execution time in ON status (μs)
Instruction
16-bit instruction
Contact instructions
LD
LDI
LDP
LDF
AND
ANI
ANP
ANF
OR
ORI
ORP
ORF
Connection instructions
ANB
ORB
MPS
MRD
MPP
INV
MEP
MEF
Output instructions
OUT Y,M
OUT S
OUT T K
912
32-bit instruction
16-bit instruction
0.42
0.42
2.72
2.76
0.41
0.41
2.72
2.76
0.42
0.42
2.72
2.76
0.41
0.41
0.42
0.41
0.38
0.38
1.73
1.81
0.42
1.65
3.19
Execution time in OFF status (μs)
32-bit instruction
2.68
2.72
2.68
2.72
2.68
2.72
1.65
2.95
B Instruction Execution Time
B-1 Basic Instruction Execution Time
Remarks
*1
1.68 μs in 2-step instruction
*3
1.68 μs in 3-step instruction
*1
1.68 μs in 2-step instruction
*3
1.68 μs in 3-step instruction
3-step instruction
2.8 μs in execution in ON status
2.76 μs in execution in OFF status
3-step instruction
2.84 μs in execution in ON status
2.8 μs in execution in OFF status
*1
1.48 μs in 2-step instruction
*3
1.52 μs in 3-step instruction
*1
1.48 μs in 2-step instruction
*3
1.52 μs in 3-step instruction
3-step instruction
2.8 μs in execution in ON status
2.76 μs in execution in OFF status
3-step instruction
2.8 μs in execution in ON status
2.76 μs in execution in OFF status
*1
1.6 μs in 2-step instruction
*3
1.6 μs in 3-step instruction
*1
1.6 μs in 2-step instruction
*3
1.6 μs in 3-step instruction
3-step instruction
2.8 μs in execution in ON status
2.76 μs in execution in OFF status
3-step instruction
2.8 μs in execution in ON status
2.76 μs in execution in OFF status
*2
1.52 μs in 2-step instruction
*3
1.56 μs in 3-step instruction
T246 to T319
3.47 μs in execution in ON status
2.82 μs in execution in OFF status
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3
*3