FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
2. Introduction of method for using flags in any positions other than directly under applied
instructions
When two or more applied instructions are programmed, general flags turn ON or OFF when each applied instruction
turns ON.
Accordingly, when using a flag in any position other than directly under an applied instruction, set to ON or OFF
another device just under the applied instruction, and then use the contact of the device as the command contact.
DSW execution
complete flag
M8029 is
changed to
M100.
DPLSY
execution
complete flag
M8029 is
changed to
M200.
M8000
FNC 72
X10
DSW
M8029
Execution is
completed
M0
FNC 57
DPLSY
M8029
Execution is
completed
It works as DSW
execution
complete flag.
M100
FNC 22
MUL
It works as
DPLSY execution
complete flag.
M200
6 What to Understand before Programming
6.5 General Rules for Applied Instructions
Y10
D0
K1
M100
K1000
D20
Y000
M0
RST
M200
D0
K10
D20
Y030
1
2
3
4
5
6
7
8
9
10
175