Mitsubishi Electric FX3G SERIES Programming Manual page 536

Programmable controllers
Hide thumbs Also See for FX3G SERIES:
Table of Contents

Advertisement

FX
/FX
/FX
Series Programmable Controllers
3G
3U
3UC
Programming Manual - Basic & Applied Instruction Edition
Related instruction
Instruction
CCD (FNC 84)
Caution
• In the 32-bit operation, the acquired sum is 64-bit data. FX
the sum is within the numeric range of 32-bit data (K-2,147,483,648 to K2,147,483,647), however, FX
PLCs can handle the low-order 32 bits of 32-bit data as the sum while ignoring the high-order 32 bits.
• Note that the 32-bit value [n+1, n] is valid when D or R is specified as "n" in a 32-bit instruction.
In the case of "DWSUM D0 D100 R0", "n" is [R1, R0].
Errors
An operation error is caused in the following cases; The error flag M8067 turns ON, and the error code is stored in
D8067.
• When "n" points starting from
• When "n" is smaller than or equivalent to "0" (error code: K6706)
• When
D
Program example
In the program shown below, the sum of 16-bit data stored in D10 to D14 is stored in [D101, D100].
X010
534
Check code
Calculates the sum of 16-bit data in units of byte (8 bits) and the horizontal parity.
are outside the specified device range (error code: K6706)
S
are outside the specified device range. (error code: K6706)
FNC140
D10
D100
WSUMP
19 Data Operation 2 – FNC140 to FNC149
19.1 FNC140 – WSUM / Sum of Word Data
Description
and FX
3U
3UC
K4500
D10
K5
K2500
D11
D12
K-3276
K6780
D13
END
K4444
D14
PLCs cannot handle 64-bit data. When
WSUMP
[D101,D100]
instruction
K14948
and FX
3U
3UC