Master Reset
Note: Device Address (5.1.)remains unchanged if the reset command is sent remotely
(via AMS, PDM, DTM, FC375) but is reset to 0 if the reset command is sent via LUI.
•
Navigate to Configure/Setup > Operation
•
In the General field click on Master Reset and accept the option Factory Defaults.
Pull-down menu access
A pull-down menu under Actions gives alternative access to several features.
Scan Device
•
Open the menu Actions – Scan Device.
•
Scan Device uploads parameters from the device (synchronizes parameters).
Device configuration
1)
Navigate to Configure/Setup > Operation and click to open the dialog window.
Master
Reset
2)
In the General field, click on Master Reset and perform a reset to Factory Defaults.
3)
Open the pull-down menu Actions – Scan Device to synchronize parameters (upload
parameters from the device to AMS).
4)
Configure the device via the Quick Start wizard.
7ML19985JE06
Action menu items
SITRANS LR250 (HART) – INSTRUCTION MANUAL