Siemens SITRANS LR250 Operating Instructions Manual page 144

Radar transmitters profibus pa
Hide thumbs Also See for SITRANS LR250:
Table of Contents

Advertisement

Parameter reference
Master Reset (4.1.)
Note
Following a Factory Reset, some degree of reprogramming may be required, depending on
the option chosen below.
Reset options
Factory Defaults
Standard Defaults
Informational
Functional
Warm Start
Reset Address to
126
To access via SIMATIC PDM:
Open the menu Device – Master Reset. For more detail see Master Reset (Page 96).
To perform a reset via the handheld programmer:
1. Press RIGHT Arrow to open Edit Mode then scroll down to the desired Reset option and
press RIGHT Arrow to select it.
2. Press LEFT Arrow to exit.
142
Result
Resets all user parameters to the manufacturer's default settings, with
certain exceptions. The list of exceptions includes, but is not limited to:
Tag
Message
Descriptor
Installation Data
Device Address
Write Protection
Auto False Echo Suppression Range
learned TVT
Resets all resettable parameters excluding device addresses to the
PROFIBUS standard default settings.
Resets Tag parameter.
Resets parameters that control device behavior and functionality (such as
calibration points)
Has the same effect as recycling power to the device
Resets the PROFIBUS device address to 126
If the address lock was on, will disable the lock.
SITRANS LR250 (PROFIBUS PA)
Operating Instructions, 08/2014, A5E32221386-AC