hit counter script

Siemens SITRANS LR250 Operating Instructions Manual page 115

Radar transmitters profibus pa
Hide thumbs Also See for SITRANS LR250:
Table of Contents

Advertisement

Sensor Offset (2.3.7.3.)
A constant offset that can be added to or subtracted from the sensor value to compensate for a
shifted sensor reference point. (For example, when adding a thicker gasket or reducing the
standoff/nozzle height.) Sensor value is the value produced by the echo processing which
represents the distance from sensor reference point to the target. (see Calibration (2.3.7.) for an
illustration).The units are defined in Unit (2.3.1.).
Values
Related parameters
Low Level Point (2.3.7.4.)
The level when the material is at Low Calibration Point. The unit is defined in Level units.
Values
High Level Point (2.3.7.5.)
The level when the material is at High Calibration Point. The unit is defined in Level units.
Values
Level Offset (2.3.7.6.)
A constant offset that can be added to Level. The unit is defined in Level units.
Values
Rate (2.3.8.)
Note
Default settings in the parameter tables are indicated with an asterisk (*) unless explicitly
stated.
SITRANS LR250 (PROFIBUS PA)
Operating Instructions, 08/2014, A5E32221386-AC
Range: -99.999 to 99.999. Default: 0.00 m
Units (2.3.1.)
Range: -999999.00 to 999999.00. Default: 0%
Range: -999999.00 to 999999.00. Default: 100%
Range: -999999.00 to 999999.00. Default: 0%
Parameter reference
113

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents