10.3

General fault codes

Note
• The status icon shown associated with each fault is the default icon in Condensed Mode.
• If more than one fault is present, the device status indicator and text for each fault
alternate at 2 second intervals.
• Some faults cause the device to go to Fail-safe mode (Fault 52). These are indicated with
an asterisk (*).
Code/
Meaning
Icon
S: 0
*
The device was unable to get a measurement
within the Fail-safe LOE Timer period. Possible
causes: faulty installation, antenna material
buildup, foaming/other adverse process
conditions, invalid configuration range.
S: 2
*
Unable to collect profile because of a power
condition that is outside the operating range of
the device.
S: 3
Device is nearing its lifetime limit according to
the value set in Reminder 1 (Required) (4.2.5.).
S: 4
Device is nearing its lifetime limit according to
the value set in Reminder 2 (Demanded)
(4.2.6.).
S: 6
Sensor is nearing its lifetime limit according to
the value set in Reminder 1 (Required) (4.3.5.).
S: 7
Sensor is nearing its lifetime limit according to
the value set in Reminder 2 (Demanded)
(4.3.6.).
SITRANS LR250 (PROFIBUS PA)
Operating Instructions, 08/2014, A5E32221386-AC
Diagnosing and troubleshooting
Corrective Action
Ensure installation details are correct.
Ensure no antenna material buildup. Clean if
necessary.
Adjust process conditions to minimize foam or other
adverse conditions.
Correct configuration range.
If fault persists, contact your local Siemens
representative.
Repair required: contact your local Siemens
representative.
Replacement is recommended.
Replacement is recommended.
Replacement is recommended.
Replacement is recommended.