hit counter script

Mitsubishi Electric FX5 User Manual page 137

Melsec iq-f series
Hide thumbs Also See for FX5:
Table of Contents

Advertisement

RS-485 communication equipment
One-pair wiring and two-pair wiring (for RS-422) are applicable for RS-485 communication. Wire according to the counterpart
equipment.
The wiring that can be used is limited by the control line setting in the communication settings (Page 136 Communication
Settings).
Control line
Bidirectional half duplex
Bidirectional full duplex
: Supported, : Not supported
■For one-pair wiring
RS-485 Communication
equipment
SDA
(TXD+)
SDB
Termination
(TXD-)
resistor
110 
RDA
*2
(RXD+)
RDB
(RXD-)
LINK
SG
Class-D grounding
*1 Make sure to perform Class-D grounding on the shield of the twisted pair cable to be connected.
*2 Make sure to provide a termination resistor at both ends of the wire. The built-in RS-485 port, FX5-485-BD and FX5-485ADP have built-
in termination resistors. Set the termination resistor selector switch to 110 .
Precautions
When the control line is set to [Bidirectional Full Duplex], the built-in RS-485 port, FX-485-BD and FX5-485ADP become a
full-duplex interface, and echo will occur.
■For two-pair wiring
RS-485/RS-422 Communication
equipment
SDA
(TXD+)
SDB
*2
(TXD-)
RDA
(RXD+)
RDB
*2
(RXD-)
Termination
LINK
resistor
SG
330  × 2
Class-D grounding
*1 Make sure to perform Class-D grounding on the shield of the twisted pair cable to be connected.
*2 Make sure to provide a termination resistor at both ends of the wire. The built-in RS-485 port, FX5-485-BD and FX5-485ADP have built-
in termination resistors. Set the termination resistor selector switch to 330 .
One-pair wiring
Built-in RS-485 port
FX5-485-BD
FX5-485ADP
SDA
(TXD+)
SDB
(TXD-)
RDA
(RXD+)
RDB
(RXD-)
SG
*1
Class-D grounding
Built-in RS-485 port
FX5-485-BD
FX5-485ADP
SDA
(TXD+)
SDB
(TXD-)
RDA
(RXD+)
RDB
(RXD-)
SG
*1
Class-D grounding
Two-pair wiring
Built-in RS-485 port
FX5-485-BD
FX5-485ADP
SDA
(TXD+)
SDB
Termination
(TXD-)
resistor
110 
RDA
*2
(RXD+)
RDB
(RXD-)
SG
*1
Built-in RS-485 port
FX5-485-BD
FX5-485ADP
SDA
(TXD+)
SDB
*2
(TXD-)
RDA
(RXD+)
RDB
*2
(RXD-)
Termination
resistor
SG
330  × 2
*1
5 NON-PROTOCOL COMMUNICATION
5
135
5.5 Wiring

Advertisement

Table of Contents
loading

Table of Contents