The devices are assigned according to the set pattern in the the refresh range setting as the following set device number (All
stations, bit device (M): 4000, word device (D): 1000) set at the head. (Page 17 Link specifications)
■Pattern 0
Station
Master
number
station
Station No.
0
Word devices
D1000
(4 points for each
to D1003
station)
■Pattern 1
Station
Master
number
station
Station No.
0
Bit devices
M4000
(32 points for each
to M4031
station)
Word devices
D1000
(4 points for each
to D1003
station)
■Pattern 2
Station
Master
number
station
Station No.
0
Bit devices
M4000
(64 points for each
to M4063
station)
Word devices
D1000
(8 points for each
to D1007
station)
Precautions
When creating a program, do not change the information in devices used by other stations. If such information is changed, the
other stations will not operate normally.
2 N:N NETWORK
26
2.7 Programming
Slave stations
Station No.
Station No.
1
2
D1010
D1020
to D1013
to D1023
Slave stations
Station No.
Station No.
1
2
M4064
M4128
to M4095
to M4159
D1010
D1020
to D1013
to D1023
Slave stations
Station No.
Station No.
1
2
M4064
M4128
to M4127
to M4191
D1010
D1020
to D1017
to D1027
Station No.
Station No.
3
4
D1030
D1040
to D1033
to D1043
Station No.
Station No.
3
4
M4192
M4256
to M4223
to M4287
D1030
D1040
to D1033
to D1043
Station No.
Station No.
3
4
M4192
M4256
to M4255
to M4319
D1030
D1040
to D1037
to D1047
Station No.
Station No.
5
6
D1050
D1060
to D1053
to D1063
Station No.
Station No.
5
6
M4320
M4384
to M4351
to M4415
D1050
D1060
to D1053
to D1063
Station No.
Station No.
5
6
M4320
M4384
to M4383
to M4447
D1050
D1060
to D1057
to D1067
Station No.
7
D1070
to D1073
Station No.
7
M4448
to M4479
D1070
to D1073
Station No.
7
M4448
to M1010
D1070
to D1077