Operation error
Operation errors pertaining to the instruction are as follows.
Operation Error Flag
SM0
SM1
ON
ON
ON
ON
Program example
Writes setting values to parameter shown in the following table for inverter (station No. 6) from PLC (CH1).
Example of program using second parameter specification code (Page 117) of FREQROL-F700P Series inverter.
Parameter No.
C2
C3
125
C4
Reading
contact
X1
Command
contact
M0
Instruction execution
completed flag
SM8029
4 INVERTER COMMUNICATION
110
4.8 Programming
Operation Error
Codes
SM56
SM8067
SD0
1810
2820
3405
3600
Name
Terminal 2 frequency setting bias
frequency
Terminal 2 frequency setting bias
Terminal 2 frequency setting gain
frequency
Terminal 2 frequency setting gain
(s1)
(s2)
IVWR
K6
K902
IVWR
K6
K1902 H64
IVWR
K6
K903 H0C8
IVWR
K6
K1903 D103
Description
SD8067
When specified channel is used with another instruction.
When specified device exceeds the device range.
When the value specified for (s1) is other than K0 to 31.
When the value specified for (s2) is outside the range that can be specified.
(Less than K0, K3000 to 9999, K13000 to 32767)
When the value specified for (n) is other than K1 to 4.
When specified channel is not setting parameter.
Second parameter
specification code
902
1902
903
1903
SET
M0
(s3)
(n)
(d)
Terminal 2 frequency setting bias frequency:
H0A
K1
M200
10 Hz
Head bit device number of instruction
execution status output
Communication channel: 1 to 4
Value written to inverter
Inverter parameter number (decimal)
Inverter station number: 0 to 31
Terminal 2 frequency setting bias: 100%
K1
M210
The unit is specified by Analog
input selection [Pr.73].
Terminal 2 frequency setting gain frequency:
K1
M220
200 Hz
Terminal 2 frequency setting gain: 100%
K1
M230
The unit is specified by Analog
input selection [Pr.73].
RST
M0
Setting values to be written
10[Hz]
100[%]
200[Hz]
100[%]