Advertisement

Ex.
Refresh range: pattern 1, link device head number: all station D1000/M4000,
Master station: FX5 PLC, slave station: FX5 PLC  3
Station number
Master station
Station No.
0
Slave stations
Station No.
1
Station No.
2
Station No.
3
In the example above, devices from D1000 to D1033 (34 points from the head device number of D) and from M4000 to M4223
(224 points from the head device number of M) are occupied. Other devices can be used as general control devices.
Link devices for unconnected slave stations can be used as general control devices; however, it is recommended to save the
unoccupied link devices for the slave stations to be used in the future.
Ex.
Refresh range: pattern 2, Link device head number: station 0 (D200/M2000), station 2 (D500/M3000)
Master station: FX5 PLC, slave station: FX5 PLC  1/FX3 PLC  2
Station number
Master station
Station No.
0
Slave stations
Station No.
1
Station No.
2
Station No.
3
The link devices are allocated as above and the link device numbers are different according to the station number (for the FX3
series, the numbers are fixed). However, the link device numbers are linked to the corresponding devices.
The link device head number of FX5 PLC can be set individually for each station; however, unifying the numbers in the system
is recommended to prevent disordered numbers.
Link time
The link time indicates the cycle time from the start of parameter message editing until link devices are updated and
parameter message editing is restarted.
The link time varies depending on the number of linked units (master station and slave stations) and the number of linked
devices as shown in the table below.
Number of linked units
2
3
4
5
6
7
8
2 N:N NETWORK
18
2.4 Specifications
Master station
Slave stations
Station No. 0 (FX5 PLC)
Station No. 1 (FX5 PLC)
D1000 to D1003
D1000 to D1003
M4000 to M4031
M4000 to M4031
D1010 to D1013
D1010 to D1013
M4064 to M4095
M4064 to M4095
D1020 to D1023
D1020 to D1023
M4128 to M4159
M4128 to M4159
D1030 to D1033
D1030 to D1033
M4192 to M4223
M4192 to M4223
Master station
Slave stations
Station No. 0 (FX5 PLC)
Station No. 1 (FX3 PLC)
D200 to D207
D0 to D7
M2000 to M2063
M1000 to M1063
D210 to D217
D10 to D17
M2064 to M2127
M1064 to M1127
D220 to D227
D20 to D27
M2128 to M2191
M1128 to M1191
D230 to D237
D30 to D37
M2192 to M2255
M1192 to M1255
Pattern 0
0 bit-device (M)
4 word-devices (D)
20 ms
29 ms
37 ms
46 ms
54 ms
63 ms
72 ms
Station No. 2 (FX5 PLC)
D1000 to D1003
M4000 to M4031
D1010 to D1013
M4064 to M4095
D1020 to D1023
M4128 to M4159
D1030 to D1033
M4192 to M4223
Station No. 2 (FX5 PLC)
D500 to D507
M3000 to M3063
D510 to D517
M3064 to M3127
D520 to D527
M3128 to M3191
D530 to D537
M3192 to M3255
Pattern 1
32 bit-devices (M)
4 word-devices (D)
24 ms
35 ms
45 ms
56 ms
67 ms
78 ms
88 ms
Station No. 3 (FX5 PLC)
D1000 to D1003
M4000 to M4031
D1010 to D1013
M4064 to M4095
D1020 to D1023
M4128 to M4159
D1030 to D1033
M4192 to M4223
Station No. 3 (FX3 PLC)
D0 to D7
M1000 to M1063
D10 to D17
M1064 to M1127
D20 to D27
M1128 to M1191
D30 to D37
M1192 to M1255
Pattern 2
64 bit-devices (M)
8 word-devices (D)
37 ms
52 ms
70 ms
87 ms
105 ms
122 ms
139 ms

Advertisement

Table of Contents
loading

Table of Contents