CPU Module Operation Setting
Specify the operation which the CPU module should perform when an error occurs on each intelligent function module.
Navigation window  [Parameter]  [System Parameter]  [I/O Assignment Setting]
Window
Displayed items
Item
CPU Module Operation
Setting at Error
Detection
LED display setting
Set whether or not to display the ERROR LED and BATTERY LED.
Navigation window  [Parameter]  [FX5UCPU]  [CPU Parameter]  "RAS Setting"  "LED Display Setting"
Window
Displayed items
Item
ERROR LED
Minor Error (Continue
Error)
BATTERY LED
Battery Error
21 RAS FUNCTIONS
158
21.1 Self-Diagnostics Function
Description
Sets the CPU module operation upon the detection of major or
moderate errors in the configured module.
Description
Sets whether or not the ERROR LED is displayed when a minor error
occurs.
Sets whether or not the BATTERY LED is displayed when a battery
error occurs.
Setting range
• Critical: Stop, Moderate:
Continue
• Critical: Stop, Moderate: Stop
• Critical: Continue, Moderate:
Continue
Setting range
• Display
• Do Not Display
• Display
• Do Not Display
Default
Critical: Stop,
Moderate: Continue
Default
Display
Display