Error codes of the CC-Link IE Field Network Basic (CFC0H to CFFFH)
The following table lists the error codes detected by the CC-Link IE Field Network Basic function.
Error
Error name
code
CFC0H
Cyclic transmission
error (master
station)
CFC1H
Cyclic transmission
error (master
station)
CFC8H
Cyclic transmission
error (master
station)
CFC9H
Cyclic transmission
error (master
station)
CFD0H
Master station error
CFD1H
Master station error
CFE0H
Cyclic transmission
error (slave station)
CFE1H
Cyclic transmission
error (slave station)
CFE8H
Cyclic transmission
error (slave station)
CFE9H
Cyclic transmission
error (slave station)
CFF0H
Slave station error
APPX
438
Appendix 3 Error Code
Error details and cause
• Unable to execute cyclic transmission because multiple
master stations exist in the same network address.
• Unable to execute cyclic transmission because the error
occurred in cyclic transmission.
• Unable to execute cyclic transmission because the slave
station controlled by other master station exists.
• Unable to execute cyclic transmission because the slave
station of the same IP address exists in the same network
address.
• The port No. (61450) used in CC-Link IE Field Network
Basic has already been used.
• Invalid value has been set in subnet mask.
• The cyclic transmission was executed for the slave station
controlled by other master station.
• The unusable number of occupied stations has been
specified from master station.
• There is no response from slave station.
• The slave station of the same IP address has existed in
the same network address.
• The error occurred in slave station.
Action
• Check the existence status of master station in network.
• Take measures to reduce noise.
• If the same error is displayed again, please contact your
local Mitsubishi representative.
• Check the existence status of master station in network.
• Check the slave station where the error occurred.
• Check the existence status of slave station in network.
• Check the slave station where the error occurred.
• Check the port No. used in Ethernet function.
• Check the parameter setting.
• Check the existence status of master station in network.
• Check the slave station where the error occurred.
• Check the number of occupied stations setting in master
station parameter (Network Configuration Settings).
• Check the slave station disconnection detection setting in
master station parameter (Network Configuration
Settings).
• Check the existence status of slave station in network.
• Check the slave station which is disconnected.
• Take measures to reduce noise.
• Check the slave station where the error occurred.
• Check the slave station where the error occurred.