hit counter script

Mitsubishi Electric FX5 User Manual page 250

Melsec iq-f series
Hide thumbs Also See for FX5:
Table of Contents

Advertisement

Functions that share inputs and outputs
When using input/output for high-speed input/output function, other high-speed input/output functions cannot be used
together depending on the combination. For positioning function, refer to MELSEC iQ-F FX5 User's Manual (Positioning
Control - CPU module built-in, High-speed pulse input/output module).
■CPU module
• Input
The following functions occupy inputs of the high-speed input/output function.
Function
*1
Input interrupt
High-speed counter
Pulse width measurement
Positioning
*1 If used simultaneously with another function, the input logic of the other function is applied.
*2 When external preset input and external enable input are used, the number of usable channels is decreased depending on the counter
type.
• Output
The following functions occupy outputs of the high-speed input/output function. The following functions cannot be combined
with other high-speed input/output functions.
Function
*1
PWM
Positioning
*1 When positioning is not used, the output devices (Y) for which the positioning setting is enabled with parameters can be used as PWM
outputs or general-purpose devices having no parameter.
Precautions
Do not specify an output device (Y) used by the high-speed input/output function as the output destination of the high-speed
comparison table. This may cause an unexpected operation.
24 HIGH-SPEED INPUT/OUTPUT FUNCTION
248
24.1 High-speed Counter Function
Interrupt (Rising)
Interrupt (Falling)
Interrupt (Rising + Falling)
Interrupt (Rising) + Pulse Catch
Input A phase
Input B phase
Input external preset
Input external enable
Near-point dog signal
Zero signal
Interrupt input signal 1 (Normal mode)
External start signal
PULSE
SIGN
CW
CCW
Clear signal
Up to CH/axis
Device
8 CH
X0 to X17
*2
8 CH
X0 to X17
4 CH
X0 to X7
4 axis
X0 to X17
4 axis
X0 to X17
4 axis
X0 to X17
4 axis
X0 to X17
Up to CH/axis
4 CH
4 axis
2 axis
4 axis
Simultaneous useable
function
The functions other than
high-speed counter (input A
phase, input B phase)
Cannot be combined
Input interrupt
Input interrupt
• Input interrupt
• Zero signal
• Input interrupt
• Near-point dog signal
Input interrupt
Input interrupt
Device
Y0 to Y7
Y0 to Y3
Y0 to Y17
Y0, Y2
Y1, Y3
Y0 to Y17

Advertisement

Table of Contents
loading

Table of Contents