26.6
File Register (R)
Device capable of storing numerical data.
26.7
Nesting (N)
Device for programming operating conditions by nesting using master control instructions (MC/MCR instruction)
conditions are specified in ascending order (N0 to N14) from outside the nesting.
Control
Control
range of
range of
nesting N1
nesting N0
*1 Instruction for creating an efficient circuit switching program by switching common bus of the circuit.
A
N0
M15
B
N1
M16
C
N2
Control
M17
range of
nesting N2
Designated in
ascending No. order
MC
N0
M15
Executed when condition
A is met
MC
N1
M16
Executed when condition
A and B are met
MC
N2
M17
Designated in
descending No. order
Executed when condition
A, B and C are met
MCR
N2
Executed when condition
A and B are met
MCR
N1
Executed when condition
A is met
MCR
N0
Executed regardless of
conditions A, B, and C
26.6 File Register (R)
26
*1
. Operation
26 DEVICES
315