Advertisement

Error
Error name
code
1FE3H
Module
configuration
error
1FE4H
Module
configuration
error
1FE5H
Module
configuration
error
1FE6H
Module
configuration
error
1FE7H
Module
configuration
error
2003H
Module
configuration
error
2008H
Module
configuration
error
2042H
CPU module
configuration
error
20E0H
Invalid module
detection
2120H
Memory card
error
2121H
Memory card
error
2160H
IP address
duplication error
2180H
Invalid file
21A0H
File specification
error
APPX
404
Appendix 3 Error Code
Error details and cause
• The module specified in the I/O
assignment setting of the parameters is
not connected.
• Parameters for a standard input/output
module are set to a high-speed pulse
input/output module.
• The I/O numbers of the reserved module
specified in the I/O assignment setting of
the parameters overlap those of other
modules.
• The I/O method of the input/output
module is different.
• The type of the CPU module is different.
• The model of the module connected is
different from that of the module set in
the parameters.
• The total number of I/O points (excluding
remote I/O) exceeded 256.
• The number of input, output, input/
output, and intelligent function modules
connected is equal to or greater than 17.
• The number of communication adapters
connected is equal to or greater than 3.
• The number of analog adapters
connected is equal to or greater than 5.
• The number of extension power supply
modules connected is equal to or greater
than 3.
• The number of expansion boards
connected is equal to or greater than 2.
• An unsupported module was detected.
• An SD memory card error was detected.
• The SD memory card may have been
removed without the SD memory card
disabled.
• An SD memory card error was detected.
• The SD memory card may not be
correctly formatted.
• The IP address is duplicated within the
system.
• An error was found in the data of the file.
• The file specified in the parameters does
not exist.
Action
• Make sure that the parameters are
consistent with the connections.
• Make sure that the parameters are
consistent with the connections.
• Make sure that the parameters are
consistent with the connections.
• Make sure that the parameters are
consistent with the connections.
• Make sure that the parameters are
consistent with the connections.
• Make sure the model of the module to be set
is consistent with the parameters of the
module connected.
• Do not use more than 256 I/O points in
programs.
• Use up to 16 input, output, input/output, and
intelligent function modules.
• Use up to 2 communication adapters.
• Use up to 4 analog adapters.
• Use up to 2 extension power supply
modules.
• Use up to 1 expansion board.
• Verify that the version of the CPU module is
compatible with the module where the error
was detected.
• If the version of the CPU module is correct,
there may be a malfunction in the connected
module. Replace the connected module.
• Check the connection of the SD memory
card. If the problem persists, there may be a
malfunction in the SD memory card or CPU
module.
• Format the SD memory card. If the problem
persists, there may be a malfunction in the
SD memory card or CPU module.
• Review the setting so that the IP address is
not duplicated within the system.
• Recreate the file.
• Rewrite the project.
Detailed
Diagnostic
information
timing
System
At power-on,
configuration
at RESET
information
System
At power-on,
configuration
at RESET
information
System
At power-on,
configuration
at RESET
information
System
At power-on,
configuration
at RESET
information
System
At power-on,
configuration
at RESET
information
System
At power-on,
configuration
at RESET
information
System
At power-on,
configuration
at RESET
information
System
At power-on,
configuration
at RESET
information
System
At power-on,
configuration
at RESET
information
Drive/file
Always
information
Drive/file
Always
information
Always
Drive/file
At power-on,
information
at RESET, at
STOP →
RUN state
Drive/file
At power-on,
information
at RESET, at
Parameter
STOP →
information
RUN state

Advertisement

Table of Contents
loading

Table of Contents