hit counter script

Mitsubishi Electric FX5 User Manual page 457

Melsec iq-f series
Hide thumbs Also See for FX5:
Table of Contents

Advertisement

Data output type
Describes each file output type.
■Binary file output format
The following figure shows the configuration of the binary format and details of each data.
• Configuration figure of binary format
(1) Identification code: Fixed to 4 bytes
(fixed to "MFCB")
(2) File version: 1 byte (fixed to 1)
(3) File type: 1 byte (fixed to 1)
(4) Model information: 16 bytes
(5) Added-data information: 2 bytes
(6) Comment size: Fixed to 2 bytes
Header
(7) Comment: (Comment size) bytes
(8) Logging target number of data points: 2 bytes
Head-logging target data information
(Logging target data points from the
second one to the second-to-last)
Last-logging target data information
(Records from the second
Data
one to the second-to-latest)
: Whether or not to export can be selected.
Head-record data
Last-record data
(9) Logging target data information size: 2 bytes
(10)
Data type: 2 bytes
(11) Output type: 2 bytes
(12) Data information setting: 2 bytes
(13) Data length: 2 bytes
(14) Data name length: 2 bytes
(15) Data name: (Data name length) bytes
(16) Record start flag (FFFFH): (2 bytes)
(17) Record data length: 2 bytes
(18) Day and time data
(19) Data acquisition interval: 8 bytes
(20) Index: 4 bytes
(21) Trigger occurrence flag: 2 bytes
(22) Head data: (Data length) bytes
(Data points from the second
one to the second-to-last)
(22) Last data: (Data length) bytes
(16) Record end flag (FFFEH): 2 bytes