hit counter script

Heating Zone Menu - Bosch CRC200 Installation Instructions For Contractors

Comfort room controller
Hide thumbs Also See for CRC200:
Table of Contents

Advertisement

8.2

Heating zone menu

Settings for the heating zone are made in this menu. With
automatic configuration, important data are preset.
Afterwards, only the relevant menu items appear in this menu.
Example: In case of outdoor reset control, the menu item for
room temperature-dependent control is not displayed.
Menu item
default setting
Design Temp
113 °F (45 °C)
(
)
Base point
77 °F (25 °C)
(
)
End point (
) 113 °F (45 °C)
(with Low Temp.
heating)
167 °F (75 °C)
(with High Temp
heating)
Max. Suppl.T.
118 °F (48 °C)
(Low Temp.
heating) | 167 °F
(75 °C) (only High
Temp)
PID charact.
Medium
Opt. pump run
NO
Table 7
Settings in the heating zone menu
CRC200
Control range
86...140 °F (30...60 °C)
(with Low Temp.
heating) | 86...185 °F
(30...85 °C) (only High
Temp)
68 °F (20 °C) ... End
point (with Low Temp.
heating)
Base point ... 140 °F
(60 °C) (with Low Temp.
heating)
Base point ... 185 °F
(85 °C) (with High Temp
heating)
86...140 °F (30...60 °C)
(with Low Temp.
heating) | 86...185 °F
(30...85 °C) (only High
Temp)
Fast | Medium | Slow
NO | YES
NOTICE: Risk of damaging or destroying the
screed!
▶ If radiant floor heating (Low Temp.) is
installed, observe the maximum supply
temperature recommended by the
manufacturer.
Functional description
Only visible if Control type = External opt. (Optimized outdoor
reset control) is selected:
This is the supply temperature requested at the outdoor design
temperature (see setting Min.outs.temp). The control range
depends on the heating system selected.
Only visible if Control type = External simple (simple outdoor
reset control) is selected:
This is the supply temperature at fixed outside temperature of
68 °F (20 °C). The range is limited by the setting of the End
point.
Only visible if Control type = External simple (simple outdoor
reset control) is selected:
This is the supply temperature requested at the outdoor design
temperature (see setting Min.outs.temp). The range is limited
by the setting of the Base point.
Maximum supply temperature; the control range depends on
the heating system selected.
Control characteristics (only visible when room temperature-
dependent control is selected):
Fast: Fast (2k P range), older home, loose construction, limited
insulation
Medium: Average (3k P range), Minimum building
requirements, medium construction
Slow: Slow (4k P range), newer home, tight construction, well
insulated
YES: Optimized pump operation active: The heating pump runs
as little as possible on the basis of the supply temperature
(available only with supply temperature control). This saves
energy but may also reduce comfort.
NO: If the system has more than one heat source installed (e. g.
a hybrid system) or a buffer storage tank is installed, this
function must be deactivated.
Service menu | 19
6 720 821 651 (2017/05)

Advertisement

Table of Contents
loading

Table of Contents