ONLINE MODULE CHANGE
7.3

Online Module Change Procedure

There are the following online module change procedures depending on whether the user
range setting has been made or not, whether the initial setting of GX Configurator-DA has
been made or not, and whether the other system exists or not.
7.3.1
(1) Conversion disable
7
- 4
7.3 Online Module Change Procedure

7.3.1 When industrial shipment setting is used and initial setting was made with GX Configurator-DA

Range setting
Industrial shipment setting
Industrial shipment setting
User range setting
User range setting
User range setting
User range setting
When industrial shipment setting is used and initial setting was
made with GX Configurator-DA
(a) Take the following steps to disable the conversion:
1) Set D/A conversion enable/disable setting (Un\G0) to All channel conversion
disable (3F
).
H
2) Turn Operating condition setting request (Y9) from off to on to stop the conver-
sion.
3) Operating condition setting completed flag (X9) turns off from on.
4) Check that the conversion is stopped by seeing the actual analog output value.
5) Turn Operating condition setting request (Y9) from on to off.
Initial setting
Other system
GX Configurator-DA
Sequence program
GX Configurator-DA
GX Configurator-DA
Sequence program
Sequence program
Reference section
-
Section 7.3.1
-
Section 7.3.2
Present
Section 7.3.3
Absent
Section 7.3.4
Present
Section 7.3.5
Absent
Section 7.3.6