ONLINE MODULE CHANGE
(3) Mounting of new module
7.3.3 When user range setting is used and initial setting was made with GX Configurator-DA (other system
(c)
After confirming that the "RUN" LED of the module has turned off, remove the
connector and dismount the module.
Always perform the dismounting procedure. If mounting confirmation is made
without the module being dismounted, the module will not start properly and the
"RUN" LED will not be lit.
(a) Mount the dismounted module and new module to the other system.
(b) Using the G(P).OGLOAD instruction, save the user set values to the CPU device.
Refer to Appendix 1.2 for the G(P).OGLOAD instruction.
(c) Using the G(P).OGSTOR instruction, restore the user set values to the module.
Refer to Appendix 1.3 for the G(P).OGSTOR instruction.
(d) Dismount the new module from the other system, mount it to the slot from where
the old module was dismounted in the original system, and install the connector.
(e) After mounting the module, click the [Execution] button and make sure that the
"RUN" LED is lit. Module READY (X0) remains off.
7.3 Online Module Change Procedure
1
2
3
4
5
6
7
8
7
- 17