7
ONLINE MODULE CHANGE
(5) Resumption of control
7.3.3 When user range setting is used and initial setting was made with GX Configurator-DA (other system
(d) Set digital values to CH
condition setting request (Y9) from off to on. Turn on CH
flag (Y1 to Y6) of the used channel to check whether proper conversion has been
made or not.
(Be careful since corresponding analog signals will be actually output.)
(a) After choosing [Diagnostics] - [Online module change] in GX Developer to
redisplay the "Online module change" dialog box, click the [Execution] button to
resume control. Module READY (X0) will be turned on.
(b) A message, "Online module change completed" appears.
Digital value (Un\G1 to Un\G6) and turn Operating
7.3 Online Module Change Procedure
Output enable/disable
7
- 19
1
2
3
4
5
6
7
8