7
ONLINE MODULE CHANGE
7
7.3 Online Module Change Procedure
- 32
7.3.6 When user range setting is used and initial setting was made with sequence program (other system is
If the buffer memory values compared with the reference table are not proper,
save and restoration of the user range cannot be executed.
Before executing module control resumption, follow the flowchart in Section 4.6
and make offset/gain setting in the device test of GX Developer.
Perform mode switching by making the setting of Mode switching setting
(Un\G158, Un\G159) and turning Operating condition setting request (Y9) from off
to on.
Note that if module control is resumed without offset/gain setting being made,
operation will be performed with the default values.