Installation Warning Statements
Translations of these warning statements appear in the Regulatory Compliance and Safety Information
for the Catalyst 2360 Switch document on Cisco.com.
Warning
To prevent the switch from overheating, do not operate it in an area that exceeds the maximum
recommended ambient temperature of 113°F (45°C). To prevent airflow restriction, allow at least 3
inches (7.6 cm) of clearance around the ventilation openings. Statement 17B
To prevent bodily injury when mounting or servicing this unit in a rack, you must take special
Warning
precautions to ensure that the system remains stable. The following guidelines are provided to ensure
your safety:
This unit should be mounted at the bottom of the rack if it is the only unit in the rack.
When mounting this unit in a partially filled rack, load the rack from the bottom to the top with the
heaviest component at the bottom of the rack.
If the rack is provided with stabilizing devices, install the stabilizers before mounting or servicing the
unit in the rack. Statement 1006
Only trained and qualified personnel should be allowed to install, replace, or service this equipment.
Warning
Statement 1030
Attaching the Brackets
Use four Phillips flat-head screws to attach the long side of the brackets to Catalyst 2360 switches in one
of three mounting positions.
OL-22149-02
Temperature around the unit does not exceed 113°F (45°C). If the switch is installed in a closed or
multirack assembly, the temperature around it might be greater than normal room temperature.
Humidity around the switch does not exceed 85 percent.
Altitude at the installation site is not greater than 10,000 feet.
For 10/100/1000 fixed ports, cable lengths from the switch to connected devices can be up to 328
feet (100 meters).
For cable lengths for small form-factor pluggable (SFP)-module connections, see the hardware
installation guide on Cisco.com and the documentation that shipped with the module.