hit counter script

GE P4A Technical Manual page 717

Micom p40 agile single br eaker multi-end current differential ied (non distance)
Table of Contents

Advertisement

P54A/B/C/E
MENU TEXT
Setting that defines the operative mode of the InterMiCOM_3 signal.
Selecting the channel response for this bit to Blocking allows fastest signalling, whereas setting to Direct offers higher security at the
expense of speed.
Selecting the channel response for this bit to Permissive offers higher dependability
IM3 FallBackMode
Setting that defines the status of IM3 signal in case of heavy noise and message synchronization being lost.
If set to 'Latching' the last valid IM3 status will be maintained until the new valid message is received.
If set to 'Default', the IM3 status, pre-defined by the user in 'IM3 DefaultValue' cell will be set. A new valid message will replace 'IM3
DefaultValue', once the channel recovers.
IM3 DefaultValue
Setting that defines the IM3 fallback status.
IM3 FrameSyncTim
Time delay after which 'IM3 DefaultValue' is applied, providing that no valid message is received in the meantime.
IM4 Cmd Type
Setting that defines the operative mode of the InterMiCOM_4 signal.
Selecting the channel response for this bit to Blocking allows fastest signalling, whereas setting to Direct offers higher security at the
expense of speed.
Selecting the channel response for this bit to Permissive offers higher dependability
IM4 FallBackMode
Setting that defines the status of IM4 signal in case of heavy noise and message synchronization being lost.
If set to 'Latching' the last valid IM4 status will be maintained until the new valid message is received.
If set to 'Default', the IM4 status, pre-defined by the user in 'IM4 DefaultValue' cell will be set. A new valid message will replace 'IM4
DefaultValue', once the channel recovers.
IM4 DefaultValue
Setting that defines the IM4 fallback status.
IM4 FrameSyncTim
Time delay after which 'IM4 DefaultValue' is applied, providing that no valid message is received in the meantime.
IM5 Cmd Type
Setting that defines the operative mode of the InterMiCOM_5 signal.
Selecting the channel response for this bit to Blocking allows fastest signalling, whereas setting to Direct offers higher security at the
expense of speed.
Selecting the channel response for this bit to Permissive offers higher dependability
IM5 FallBackMode
Setting that defines the status of IM5 signal in case of heavy noise and message synchronization being lost.
If set to 'Latching' the last valid IM5 status will be maintained until the new valid message is received.
If set to 'Default', the IM5 status, pre-defined by the user in 'IM5 DefaultValue' cell will be set. A new valid message will replace 'IM5
DefaultValue', once the channel recovers.
IM5 DefaultValue
Setting that defines the IM5 fallback status.
IM5 FrameSyncTim
Time delay after which 'IM5 DefaultValue' is applied.
IM6 Cmd Type
P54xMED-TM-EN-1
COL
ROW
DEFAULT SETTING
16
21
Default
16
22
1
16
23
1.5
16
28
Blocking
16
29
Default
16
2A
1
16
2B
1.5
16
30
Direct
16
31
Default
16
32
0
16
33
1.5
16
38
Direct
DESCRIPTION
Default
Latched
[Indexed String]
0 or 1
[Unsigned Integer(16 bit)]
From 0.01 to 1 in steps of 0.01
[Courier Number (time-seconds)]
Disabled
Direct
Blocking
[Indexed String]
Default
Latched
[Indexed String]
0 or 1
[Unsigned Integer(16 bit)]
From 0.01 to 1 in steps of 0.01
[Courier Number (time-seconds)]
Disabled
Permissive
Direct
[Indexed String]
Default
Latched
[Indexed String]
0 or 1
[Unsigned Integer(16 bit)]
From 0.01 to 1 in steps of 0.01
[Courier Number (time-seconds)]
Disabled
Permissive
Appendix B - Settings and Signals
AVAILABLE OPTIONS
B151

Advertisement

Table of Contents
loading

This manual is also suitable for:

P54bP54eP54c