Output Status Setting For Cpu Module Stop; When The Output Setting During Cpu Stop Is Set To Clear; When Refreshing Data By A Link Direct Device - Mitsubishi Electric QJ71GF11-T2 User Manual

Melsec-q series cc-link ie field network master/ local module
Table of Contents

Advertisement

8.1.8

Output status setting for CPU module STOP

When the CPU module mounted with a master/local module is set to STOP, whether cyclic data output is held or
cleared can be selected.
(1) Range where the setting becomes enabled
The setting is fixed to hold or clear depending on devices set to link refresh, regardless of the output setting
during CPU STOP.
The following table shows the relationship between the output status of the device set to link refresh and output
setting during CPU STOP.
Link refresh device
RY
RWw
(2) Setting method
Set the output status for the case where the CPU module switch is set to STOP. Select hold or clear in the
"Network Operation Settings" window. (
(3) Precautions
(a) When the output setting during CPU STOP is set to clear
When the CPU module is in the STOP status, the forced output to slave stations cannot be executed using GX
Works2.
(b) When refreshing data by a link direct device
The output status of when the CPU module is set to STOP is the status set for the network operation settings.
142
Y
Other devices
All devices where the output setting
during CPU STOP can be set
Output setting during CPU STOP
Hold
Clear
Hold
Hold
Page 101, Section 7.4)
Clear (ALL OFF)
Clear
Clear
Hold