● CC-Link IE Field Network gateway setting
Through a module, such as an Ethernet adapter module, where the CC-Link IE Field Network gateway setting can be
configured, any IP address can be used for the Ethernet device side. (
8.3.7 (2)
Note, however, that the network addresses on the CC-Link IE Field Network side must be the same.
For the IP address setting range, refer to the following table.
Device to be set
Ethernet device
Module supporting the CC-
Link IE Field Network gateway
setting
Master/local module
Universal model QCPU on the
communication route (not
connected to an Ethernet
device)
● When setting the IP address in each device, do not use the IP addresses already used for other devices.
Setting range of the IP address
First and second octets
Within the range applicable to the Ethernet device
Within the range applicable to the module supporting the CC-Link IE Field Network gateway
setting (
Manual for the module supporting the CC-Link IE Field Network gateway
setting used)
0.0 to 255.255
IP address setting not required
Page 158, Section 8.3.4, Page 166, Section
Third octet
Automatically set (station
Automatically set (network
number of the own station)
number of the own station)
1 to 120
1 to 239
125 (125 is always set
in the master station.)
CHAPTER 8 FUNCTIONS
Fourth octet
151
8