Mitsubishi Electric QJ71GF11-T2 User Manual page 156

Melsec-q series cc-link ie field network master/ local module
Table of Contents

Advertisement

● When an Ethernet device is connected to a module, such as an Ethernet adapter module, that does not support the
routing parameters
Set the routing parameters so that communications are transmitted through the master station.
Communications from a module that does not have the routing parameters are automatically transmitted through the
master station. The communication routes must be the same for data sending and receiving; therefore, configure the
setting so that communications are transmitted through the master station.
Proper setting
Ex.
Ethernet device
(request source device)
A
Setting for
Target
Network No.
3
Set this column to pass communications
Improper setting
Ex.
Ethernet device
(request source device)
A
Setting for
Target
Relay
Network No.
Network No.
3
Because the communication route for data sending is different
from that for data receiving, an error occurs.*
*1
An IP communication test related error (error code: 4A28
154
Local station
A
Station
No.1
Network No.1
Setting for
Relay
Relay
Target
Network No.
Station No.
Network No.
0
2
through the master station.
Local station
A
Station
No.1
Network No.1
Setting for
Relay
Target
Station No.
Network No.
2
2
Master station
Station
No.0
B
C
Station
No.2
Network No.2
Communication routes set using the routing
parameters
Communication route automatically set
(from a module that does not have the routing
parameters to the master station)
B
Relay
Relay
Network No.
Station No.
1
2
1
3
2
2
Master station
Station
No.0
B
C
Station
No.2
Network No.2
Communication routes set using the routing
parameters
Communication route automatically set
(from a module that does not have the routing
parameters to the master station)
B
Relay
Relay
Network No.
Station No.
1
2
1
1
) occurs in the IP communication test.
H
Ethernet device
(request destination device)
Network No.3
C
Setting for
The setting is not required
because the module does not
have the routing parameters.
Ethernet device
(request destination device)
Network No.3
C
Setting for
The setting is not required
because the module does not
have the routing parameters.