Setting In The Cpu Module 2, Local Station 1 (Station Number 2), And Master Station 2 (Station Number 0) - Mitsubishi Electric QJ71GF11-T2 User Manual

Melsec-q series cc-link ie field network master/ local module
Table of Contents

Advertisement

(c) Setting in the CPU module 2, local station 1 (station number 2), and master station 2
(station number 0)
1.
Set the routing parameters to the CPU module 2.
Project window
MELSECNET]
2.
Set the IP address in the master station 2 (station number 0).
Project window
MELSECNET]
3.
The IP address setting is not required for the local station 1 (station number 2).
The network address set in the master station 1 (station number 0) is automatically assigned.
4.
Write the set parameters to the CPU module 2. Then reset the CPU module 2 or power off and on
the system.
[Online]
[Write to PLC]
[Parameter]
[Network Parameter]
button
[Parameter]
[Network Parameter]
button
RESET
or Power OFF
CHAPTER 8 FUNCTIONS
[Ethernet/CC IE/
[Ethernet/CC IE/
ON
8
169