(a) Control data
Device
Item
Execution/
(S1)+0
abnormal end type
(S1)+1
Completion status
284
Setting data
b15
to
0
1) Execution type (bit 0)
0: Without arrival confirmation
• When the target station is on the same network
The process is completed when data is sent from the own
station.
Request
source
• When the target station is on another network
The process is completed when data arrives at the relay station
on the same network.
Request
source
Completed
1: With arrival confirmation
The process is completed when data is stored in the specified
channel of the target station.
Request
source
Completed
Target
station
When "0: Without arrival confirmation" is specified, the result is
regarded as normal on the own station even if the transmission to the
target station fails as follows.
• When communication ends normally even though sent data are
abnormal
• When data cannot be stored in the target station, because
instructions are executed to the same station from multiple stations
(The target station generates an error code (D202
2) Abnormal end type (bit 7)
Specify the data set status in case of abnormal end.
0: After (S1)+11, no data is set for abnormal end.
1: Data at the time of abnormal end is set in the area starting from
(S1)+11.
The status of when the instruction is ended is stored.
0: Normal
Values other than 0: Error (
b7
to
b0
2
0
1
Target
station
Completed
Relay
Target
station
station
Completed
Target
Relay
station
station
or D282
H
Page 439, Section 12.5)
Setting range
0000
H
0001
H
0080
H
0081
H
))
H
Set by
User
System