2.
Add the master/local module under "I/O Assignment".
3.
Click the
4.
Enter the network number for "Switch 1", 31FF
"Switch 5".
5.
Create a CCPASET instruction program. (
6.
Create a UINI instruction program. (
7.
Write the CCPASET instruction program and UINI instruction program to the CPU module through
GX Works2.
[Online]
8.
Execute the CCPASET instruction.
9.
Execute the UINI instruction in the CPU module on the local station (own station).
The UINI instruction can be executed both before and after execution of the CCPASET instruction.
(2) Clearing the station number
The station number set using the UINI instruction can be cleared by resetting the CPU module or powering off
and on the system.
(3) Precautions
(a) CPU module, master/local module, GX Works2
Before setting a station number using the UINI instruction, check the versions of the CPU module, master/local
module, and GX Works2. (
(b) Station where the UINI instruction can be executed
The UINI instruction can be executed on local stations (cannot be executed on other stations) with no station
number setting.
(c) When the station number set using the UINI instruction has already been assigned
If the station number set for a local station using the UINI instruction has already been assigned for another
station during data link, the instruction execution fails. Set a unique station number.
Note that such error cannot be detected before data link start (e.g. absence of the master station).
button.
Page 382, Section 10.18.2)
[Write to PLC]
Page 546, Appendix 8)
CHAPTER 10 DEDICATED INSTRUCTIONS
for "Switch 2", and 0000
H
H
Page 364, Section 10.17.2)
for "Switch 3" to
381
10