12.5
Error Code List
Error codes of the master/local module are listed below.
Error code
4000
H
Error detected in a CPU module
to
(
User's manual for the CPU module used))
4FFF
H
7000
H
Error detected in a module such as a serial communication module
to
(
User's manual for the serial communication module used)
7FFF
H
B000
H
Error detected in a CC-Link system
to
(
User's manual for the CC-Link system master/local module used)
BFFF
H
Error detected in an Ethernet interface module
C000
H
(
User's manual for the Ethernet interface module used,
to
QnUCPU User's Manual (Communication via Built-in Ethernet Port),
CFFF
H
MELSEC-L CPU Module User's Manual (Built-In Ethernet Function))
D000
to D007
Network module failure
H
H
D00F
Network module failure
H
D010
Parameter error (RX size over)
H
D011
Parameter error (RY size over)
H
D012
Parameter error (RWw size over)
H
D013
Parameter error (RWr size over)
H
D014
to D016
Network module failure
H
H
Parameter error (constant link scan
D018
H
time error)
D019
to D01C
Network module failure
H
H
Error
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
Correct the points assigned to the RX devices.
Correct the points assigned to the RY devices.
Correct the points assigned to the RWw devices.
Correct the points assigned to the RWr devices.
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
Correct the constant link scan time.
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
CHAPTER 12 TROUBLESHOOTING
Action
12
439