Appendix 2.2
This buffer memory stores the start number and the number of points of RX for each station.
The offset and size of buffer memory areas for each station number (other than a station number 0) can be calculated
using the following formulas:
• Offset buffer memory address = 19456 + (station No.-1) × 2
• Size buffer memory address = 19457 + (station No.-1) × 2
Appendix 2.3
This buffer memory stores the start number and the number of points of RY for each station.
The offset and size of buffer memory areas for each station number (other than a station number 0) can be calculated
using the following formulas:
• Offset buffer memory address = 19712 + (station No.-1) × 2
• Size buffer memory address = 19713 + (station No.-1) × 2
468
RX offset/size information (Un\G19456 to
Un\G19697)
Un\G19456
Station No.1
Station No.1
Un\G19457
Un\G19458
Station No.2
Un\G19459
Station No.2
Un\G19694
Station No.120
Station No.120
Un\G19695
Un\G19696
Station No.0
Station No.0
Un\G19697
RY offset/size information (Un\G19712 to
Un\G19953)
Un\G19712
Station No.1
Un\G19713
Station No.1
Un\G19714
Station No.2
Un\G19715
Station No.2
Un\G19950
Station No.120
Station No.120
Un\G19951
Un\G19952
Station No.0
Un\G19953
Station No.0
Offset
Size (in units of words)
Offset
Size (in units of words)
Offset
Size (in units of words)
Offset
Size (in units of words)
Offset
Size (in units of words)
Offset
Size (in units of words)
Offset
Size (in units of words)
Offset
Size (in units of words)

Advertisement

Table of Contents
loading

Table of Contents