Mitsubishi Electric QJ71GF11-T2 User Manual page 498

Melsec-q series cc-link ie field network master/ local module
Table of Contents

Advertisement

Number
Name
SW0043
Mode status
SW0044
Submaster station No.
SW0046
Module type
Baton pass status (own
SW0047
station)
Cause of baton pass
SW0048
interruption
496
Description
Stores the mode of own station.
0: Online (Normal Mode)
(Local station: Online)
1: Online (High Speed Mode)
2: Offline
6: Loop test
7: Self-loopback test
9: Hardware test
Stores the submaster station number that has been set using a
parameter.
Range: 1 to 120
Stores the own station's hardware status.
b15
SW0046 0
Stores the baton pass status for the own station (transient transmission
possible).
0: Data link in progress
2: Baton pass in progress
3: Baton pass stopped
4: Test in progress
5: Offline
Stores the cause of interruption in the communication (baton pass) of
own station.
00
: At normal communication or power-on
H
30
: Cable disconnection
H
33
: Disconnection or reconnection in progress
H
40
: Offline mode
H
41
: Hardware test
H
42
: Self-loopback test
H
to
b2 b1 b0
0
to
Module type
00: Module
01: Board
10: HMI
Availability
Master
station
Local
(submaster
station
station)