Electrical Connection; Maintenance; Installation And Operation - Siemens SITRANS P 7MF1562 Operating Instructions

Z series pressure transmitter
Table of Contents

Advertisement

Available languages

Available languages

2 Installation and Operation

WARNING
This device may only be installed and operated when qualified
personnel has made sure that suitable power supplies are used
which ensure no dangerous voltages can get into the device
during normal operation or in the event of an error.
The device can be operated with high pressure. Therefore
serious injury and/or considerable damage to property cannot
be totally ruled out in the event of incorrect handling.
Perfect and reliable functioning of this device depends on
proper transport, storage, installation and assembly as well as
on careful operation and maintenance.
Figure 3 Transmitter Type 7MF1562, Dimensions
2.1 Installation
a)
Figure 4 Transmitter 7MF1562, Installation
There are two installation possibilities (Figure 4):
a) at process connection G½A external thread
b) at process connection G?A internal thread
The position of the device has no influence on the measuring
accuracy.
The permissible temperature limits may not be exceeded. The
process data must be compared with the data on the rating plate
before installation.
4
b)

2.2 Electrical Connection

The shielded cable must be inserted with two wires through the
screw-type cable gland Pg 9. Only earth the shield of the cable
at one point (preferably in the terminal box). The earth is
connected to the housing.
Terminals 1 (+) 2 (-)
Earth
Output current I
Power supply U
o
Figure 5 Transmitter Type 7MF1562, Connection diagram
2.3 Setting
The transmitter is set to the respective range at the factory.
If an additional setting is necessary, the top part with the grip
ring of the connector must be removed.
The output current for the start of scale (4 mA) is set with the Z
potentiometer and the output current for the full scale (20 mA)
.
with the S ˙potentiometer
Figure 6 Transmitter7MF1562, Setting
If the start of scale is set, the span does not change!
(Span = full scale – start of scale)
The start of scale and span can be changed by ± 10% of the set
range.

2.4 Maintenance

The transmitter is maintenance-free.
The start of scale of the device should be checked occasionally.
Load R
B
L
7MF1562