hit counter script

Performance Specifications - Mitsubishi Electric AJ65BTS-RPH User Manual

Cc-link system spring clamp termnal block type repeater hub module
Table of Contents

Advertisement

3.2 Performance specifications

The performance specifications of the AJ65BTS-RPH module are
shown below.
Item
Station number
CC-Link station
type
Number of
occupied stations
Transmission rate
No. of connectable
slave stations
Max. No. of
modules connected
to the trunk line
Connection position
Max. number of
stages connected
to configure
segment
Max. transmission
distance of each
segment
Terminating resistor
Terminal block
Applicable cable
size
Applicable
solderless
terminal
Table 3.2 Performance specifications (1/2)
Can select from 156kbps / 625kbps / 2.5Mbps / 5Mbps / 10Mbps
The total number of modules connected to a trunk line and branch line
shall conform to the maximum number of connectable modules of the
master module used.
For details, refer to the user's manual of the master modules used.
Trunk
No restriction (compliant with the CC-Link specifications)
line side
Branch
Connect to the end of the branch line (segment end)
line side
AJ65BTS-RPH only (Refer to Section 2.3(3))
Combination of AJ65BTS-RPH and AJ65SBT-RPT (Refer to
Section 2.3 (4))
Combination of AJ65BTS-RPH and one of AJ65FBTA-RPH,
AJ65SBT-RPS/RPG, or AJ65BT-RPI (Refer to Section 2.3
(4))
Varies according to transmission rate (Refer to Section 3.4.).
Trunk
line side
Branch
line side
AWG #24 to 12, φ0.5 to 1.78mm single cable,
Specifications
- (none)
- (none)
0 (none)
64 (Refer to Section 2.3(2))
110Ω, or 130Ω can be selected.
110Ω (built-in)
Spring clamp terminal block
2
0.2 to 2.5mm
stranded cable
Refer to table 3.3
14
2nd stage
3rd stage
2nd stage

Hide quick links:

Advertisement

Table of Contents
loading