Siemens SITRANS FUS380 Operating Instructions Manual
Siemens SITRANS FUS380 Operating Instructions Manual

Siemens SITRANS FUS380 Operating Instructions Manual

Ultrasonic flowmeter
Hide thumbs Also See for SITRANS FUS380:

Advertisement

s
SITRANS F US
Ultrasonic flowmeter type SITRANS FUS380
Ultrasonic flowmeter type SITRANS FUE380
(type-approved for heat metering)
Technical Documentation (handbooks, instructions, manuals etc.) for the complete product
range SITRANS F can be found on the internet/intranet via the following link:
English: http://www4.ad.siemens.de/WW/view/en/10806951/133300
Order no.: A5E00730100
SFIDK.PS.022.Q5.02
[

Operating Instructions

Edition 09/2007 - Revision 05
A5E00730100
]

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SITRANS FUS380

  • Page 1: Operating Instructions

    Operating Instructions Edition 09/2007 - Revision 05 SITRANS F US Ultrasonic flowmeter type SITRANS FUS380 Ultrasonic flowmeter type SITRANS FUE380 (type-approved for heat metering) Technical Documentation (handbooks, instructions, manuals etc.) for the complete product range SITRANS F can be found on the internet/intranet via the following link: English: http://www4.ad.siemens.de/WW/view/en/10806951/133300...
  • Page 2: Table Of Contents

    Introduction General safety instructions Description Installation Electrical connection Operation Troubleshooting Sealing Technical data Ordering Appendix SFIDK.PS.022.Q5.02...
  • Page 3 Technical data SITRANS FUS380 and FUE380 ........
  • Page 4: Introduction

    For applications involving high working pressures or media that can be dangerous to people, surroundings, equipment or other in the event of pipe fracture, Siemens recommends taking precautions such as special placement, shielding or installation of a safety guard or safety valve prior to installation of the sensor.
  • Page 5 Do not unscrew the transducers during pipe operation (especially for DN 50 ... DN 80). Battery operation: • When battery operated, SITRANS FUS380 and FUE380 is not covered by the „Low Voltage Directive“ (LVD). Hence, an installation can be considered in conformance with LVD, only when the SITRANS FUS380 /FUE380 is connected to equipment conforming to LVD.
  • Page 6: Description

    FUE380 may be marked „neutral“ or have a country-specific approval label, depending on selection of flowmeter setup when ordering. Both flowmeter types SITRANS FUS380 and FUE380 are available in either compact or remote versions and electrical wiring and operation are identical for both types. The maximum permissible distance between sensor and transmitter is 30 meters.
  • Page 7: Installation

    Installation Installation of sensor compact/remote versions Requirement for straight inlet before flowmeter In order to maximise performance it is necessary to have straight inlet and outlet flow conditions before and after the flowmeter. Furthermore, a minimum distance between flowmeter and pumps and valves must be respected.
  • Page 8 The flowmeter pipe section may be installed in either a horizontal or vertical position. Note To obtain maximum battery lifetime with the Lithium Thionyl Chloride battery pack, Siemens recommends installing the flowmeter transmitter in an upright position. SFIDK.PS.022.Q5.02...
  • Page 9: Installation Of Transmitter Compact/Remote Versions

    4.2.1 General information The transmitter is packed separately - ready for plug-in into the base part. SITRANS FUS380 and FUE380 may be mains powered or battery powered. Determine the flowmeter power source type by reading the label or via the product code.
  • Page 10: Mains Powered Units With Back-Up Battery

    Do not touch the rear of the printed circuit board. 4.2.5 Mains powered units with back-up battery If SITRANS FUS380 and FUE380 is mains powered, a battery can be inserted as back-up power supply to ensure continuous operation in the event of power failure. Depending on duration and numbers of mains power failures, the battery has a lifetime of minimum 6 years (one battery).
  • Page 11: Battery Powered Version

    Battery powered version SITRANS FUS380 and FUE380 is prepared for up to 2 batteries of 3.6 V. When two batteries are installed in the battery pack it will have an operation life of minimum 6 years under normal temperature conditions (please refer to FI01 catalog).
  • Page 12: Installation Of The Transmitter, Remote Version

    Fig. 3 4.4.2 Connection of transducer cables SITRANS FUS380 and FUE380 is supplied with 4 separate cables. Cables can be used on all transducers. (The cables are not paired with a specific transducer). Snap out the connection plate and loosen grounding wire.
  • Page 13: Transducer Connection Scheme

    4.4.3 Transducer connection scheme Cables 1A and 1B first track, 1A upstream, 1B downstream. Cables 2A and 2B second track, 2A upstream, 2B downstream. Note Do not change the length of the four cables, as this will influence the accuracy of the unit. 4.4.4 Wiring diagram, base of connection board SFIDK.PS.022.Q5.02...
  • Page 14: Electrical Connection

    Electrical connection Pulse output A and B setting Install the pulse cable through the glands, before pushing the printed circuit board back into place in the base part. For compact version, install the pulse cables and power supply cable through the gland without remove the printed circuit board.
  • Page 15: Fus380 And Fue380 Preset Output B Settings

    5.1.2 FUS380 and FUE380 preset output B settings Output B, terminals 66/67: SITRANS FUS380 and FUE380 Preset to alarm indication - see Fig. 1: Example: If track 1 is not measuring, a „triangle“ alert appears on the display. The failure code „F1“...
  • Page 16: Wiring Diagram For Connection To Energy Calculator Type Sitrans Fue950

    5.1.3 Wiring diagram for connection to energy calculator type SITRANS FUE950 Connection to energy calculator SITRANS FUE950 Max. cable length between energy calculator SITRANS FUE950 and SITRANS FUE380 = 20 meter. Important Pulse output from the flowmeter must correspond to pulse input setting on the energy calculator.
  • Page 17: Operation

    Operation Flowmeter operation via key and display After fitting new batteries, reset the internal power calculation counter to correctly indicate the power capacity. When new batteries are installed, the flowmeter startup routine begins. First, the display shows the active software version. Then the message „reset.bat“ will appear. Press the key within six seconds to reset the internal counter.
  • Page 18: Operator Menu

    Operator menu Menu 1 Flow volume totalizer 1. Battery icon shows full. Menu 2 (FUS380 only) Flow volume totalizer 2 (factory configured for reverse flow). Negative values indicate reverse flow calculation. Menu 3 Actual flow rate. Negative values indicate reverse flow. Menu 4 Failure information.
  • Page 19: Troubleshooting

    Information symbols The status information symbols show the actual status of important flowmeter elements. The warning symbol appears when the ultrasonic sensors do not measure or when a failure occurs according to menu 4. The warning symbol disappears when the problem is rectified.
  • Page 20: Sealing

    Sealing User sealing of the SITRANS FUE380 Transmittter Sensor (new sealing) DN 100...1200 Transmittter Sensor (older sealing) DN 50...80 Verification sealing of the SITRANS FUE380 Transmitter Verfication sealing bottom of transmitter Verfication sealing under frame SFIDK.PS.022.Q5.02...
  • Page 21: Technical Data

    Technical data Technical data SITRANS FUS380 and FUE380 Description Specification Transmitter FUS080 Enclosure IP67 according to EN 60529 and DIN 40050 (NEMA 4X/6) Ambient temperature 0 °C …60 °C (32 °F…. 140 °F) −35 °C…85 °C (−40 °F…185 °F) Storage temperature Installation Cable max.
  • Page 22: Dimensional Drawings For Fus380 And Fue380

    Dimensional drawings for FUS380 and FUE380 Transmitter IP67/NEMA 4X/6, wall mounting 9.2.1 Pipe dimensions for FUS380 and FUE380 Size PN 16 PN 25 PN 40 Weight Weight Weight Lift 300 +0-2 300 +0-2 350 +0-2 350+0-2 350+0-3 350+0-2 350+0-3 500+0-3 500+0-3 500+0-3 500+0-3...
  • Page 23 Size PN 16 PN 25 PN 40 Weight Weight Weight Lift inch inch inch inch inch inch inch 2" 12 +0-0.08 2 1/2" - 12 +0-0.08 14.4 3" 14 +0-0.08 14.8 13.77+0-0.08 13.77+0-0.12 8.66 7.09 13.77+0-0.08 13.77+0-0.12 15.2 9.84 8.27 19.68+0-0.12 19.68+0-0.12 15.6...
  • Page 24: Ordering

    Ordering 10.1 FUS380 selection and ordering data Order-No. Order code Order-No. Order code Flowmeter SITRANS FUS380 7ME 3 4 0 0 - Flowmeter SITRANS FUS380 7ME 3 4 0 0 - (standard) (standard) max. flow range Flange norm and pressure rating...
  • Page 25 Order code Please add „-Z“ to order No. and following add-on code(s) with plain text Accredited Siemens calibration FUS380 Accredited Siemens ISO/IEC 17025 calibration. Max. flow 50 ... 250 m /h, depending on dimension (DN 50...200) Accredited Siemens ISO/IEC 17025 calibration.
  • Page 26: Fue380 (Type Approved) Selection And Ordering Data

    10.2 FUE380 (type approved) selection and ordering data Order-No. Order code Order-No. Order code Flowmeter SITRANS FUE380 7ME 3 4 1 0 - Flowmeter SITRANS FUE380 7ME 3 4 1 0 - (type approved) (type approved) max. flow range Flange norm and pressure rating Diameter Qp [m Qs [m...
  • Page 27 Max. flow 1400 ... 4200 m /h, depending on dimension China Accredited Siemens calibration FUE380 MID-Approval (EN 1434/OIML R75), English Accredited Siemens ISO/IEC 17025 calibration. MID-Approval (EN 1434/OIML R75), German Max. flow 50 ... 250 m /h, depending on dimension MID-Approval (EN 1434/OIML R75), Polish (DN 50...200)
  • Page 28: Spare Parts For Fus380 And Fue380

    PROFIBUS DP/PA or HART modem, incl. 1 TAG Cannot be expanded by further functions or TAG option/power- pack; 5 languages (German, English, French, Spanish, Italian) executes with Windows 2000 Professional or Windows XP Professional Downloads for DEVICE description FUE380: http:/support.automation.siemens.com/WW/view/en/17320235 SFIDK.PS.022.Q5.02...
  • Page 29: Appendix

    DELLSONICS 北京迪妙声科技有限公司 BEJING DELLSONICS SCIENCE & TECHNOLOGY LTD. 公 司 简 介 北京迪妙声科技有限公司(原名北京妙声力科技有限公司) ,位于北京市海淀区中关村 南大街,是与西门子公司德国总部正式签约的西门子过程仪表及分析仪器核心合作伙伴, 也是西门子北方区域规模最大、实力最强的优秀代理商。 公司主营: 一、 西门子-妙声力(Milltronics)系列物位产品:超声波物位计、超声波液位差计、超声波泥水界 面计、超声波明渠流量计、雷达物位计、射频导纳物位计、射频导纳油水界面计、 ;射频导纳物位开关、 音叉式物位开关、阻旋式物位开关;皮带称、固体质量流量计、冲板流量计等。 二、 西门子过程仪表产品:电磁流量计、质量流量计、超声波流量计、 温度变送器、压力变送器、 阀门定位器、气体分析仪等。 三、 德国 UWT 公司的阻旋式料位开关、音叉式料位开关、重锤式料位计等产品。 四、 自行研发生产超声波液位计、温度变送器、压力变送器、数显表及油田专用仪器等产品。 成立于 1954 年的西门子-妙声力公司 是世界公认的超声波物位测量领域 (Milltronics) 的领导者, 全球最大的超声波物位仪表生产厂家, 在超声波、 雷达、 电容技术领域拥有超过 60 项专利,超声波产品的综合性能指标经美国《控制》杂志评比,其综合性能名列全球第一!...