Mitsubishi Electric FX5 User Manual page 155

Melsec iq-f series, ethernet communication
Hide thumbs Also See for FX5:
Table of Contents

Advertisement

Error code
Error details and causes
(Hexadecimal)
CF10H
Incorrect frame is received.
CF20H
• The setting value of the communication setting is out of range.
• The items of communication setting which cannot be set on the
target device are set.
• The required setting items have not been set to the target
device.
CF30H
The parameter which is not supported by the target device was
specified.
CF31H
Incorrect frame is received.
CF70H
An error occurred on the Ethernet communication path.
CF71H
A timeout error has occurred.
Action
• Check the operating status and connection status of the target
device.
• Check the connection of an Ethernet cable and a hub.
• Check the line status of Ethernet.
• Reset the CPU module and target device, and retry the operation.
If the above actions do not solve the problem, contact the
manufacturer of the target device.
Correct the setting details, and retry the operation.
Check the version of the target device.
• Check the operating status and connection status of the target
device.
• Check the connection of an Ethernet cable and a hub.
• Check the line status of Ethernet.
• Reset the CPU module and target device, and retry the operation.
If the above actions do not solve the problem, contact the
manufacturer of the target device.
• Check the operation of the target device.
• Check if the connection cable is disconnected.
• Check the operation of the target device. Since there may be
congestion of packets on the line, perform the operation after a
while.
• Correct the setting details of when the iQSS function is executed,
and retry the operation.
• Check the connection of an Ethernet cable and a hub.
13 TROUBLESHOOTING
13
153
13.4 Error Codes