hit counter script

When Parameters Cannot Be Written From Gx Configurator-Dp - Mitsubishi Electric Melsec Q Series User Manual

Profibus-dp master module
Hide thumbs Also See for Melsec Q Series:
Table of Contents

Advertisement

9
TROUBLESHOOTING

9.2 When Parameters cannot be Written from GX Configurator-DP

The following shows the troubleshooting procedures to be taken when parameters cannot
be written to the QJ71PB92V from GX Configurator-DP.
(1) When the QJ71PB92D-compatible function is disabled
Parameters cannot be written.
Is the DP-Master set to "QJ71PB92V"
in the "PROFIBUS Network" window
in GX Configurator-DP?
Has settings configured in
the "Transfer Setup" window and
the "Master Settings" window
in GX Configurator-DP?
Is a blank (no setting) set for
Switch 2 of the intelligent function module switches
in GX Works2?
9
- 4
9.2 When Parameters cannot be Written from GX Configurator-DP
Yes
Yes
Yes
Completed
Figure 9.3 When the QJ71PB92D-Compatible Function is Disabled
No
Set the DP-Master to "QJ71PB92V" in the "Change Master
Type" window in GX Configurator-DP.
1) Check the settings in the "Transfer Setup" window.
No
2) Check the "Starting I/O number" setting in the "Master
Settings" window.
1) Set a blank (no setting) for Switch 2 of the intelligent
No
function module switches in GX Works2.
2) Write the PLC parameters to the QCPU.
3) Reset the QCPU, or power it OFF and then ON.

Advertisement

Table of Contents
loading

Table of Contents