Mitsubishi Electric Melsec Q Series User Manual page 161

Profibus-dp master module
Hide thumbs Also See for Melsec Q Series:
Table of Contents

Advertisement

5
SETTINGS AND PROCEDURES BEFORE SYSTEM
OPERATION
(2) Execution result of self-diagnostics
(a) TEST LED OFF (When normally completed)
(b) TEST and FAULT LEDs ON (When failed)
(c) Values that may be stored in the Offline test status area (Un\G2258)
When the TEST LED turns OFF after execution of self-diagnostics, this indicates
a normal completion.
If the TEST and FAULT LEDs are ON after execution of self-diagnostics, this
indicates that the diagnostics failed.
Check the value stored in the Offline test status area (Un\G2258), and retry the
self-diagnostics.
If the diagnostics fails again, a QJ71PB92V hardware error is probable.
Please check the value currently stored in the Offline test status area (Un\G2258),
and consult your local Mitsubishi representative.
Any of the following values is stored in the Offline test status area (Un\G2258)
after execution of self-diagnostics.
Stored Value
07FF
Normal completion
H
F700
ROM check test error
H
F701
Timer test error
H
F702
MPU test error
H
F703
RAM test error
H
F704
2-port RAM test error
H
F705
Swap port test error
H
5.4 Self-diagnostics
Table5.5 Self-diagnostics Result
Description
1
2
3
4
5
6
7
8
5
- 8