Advertisement

PRE-INSTALLATION

HNET
Siemens Industry, Inc.
Building Technologies Division
Alternate Language Custom Message
Device Usage
ZIC Circuit Usage
Degrade Mode Alarm Activation
Silenceable Option
Wiring Type
Total Current Drawn
Some restrictions apply to certain usage selections that are enforced by the Zeus
tool during Edit mode or Compile time.
Refer to the Zeus Quick Start Manual, P/N 315-033875, or the Zeus self-help index
for more information.
The following components must be set prior to inserting the card into the CC-5/CC-2
(refer to Figure 2):
S2, Reset Switch: Momentarily Closed
switch that when pressed will initiate a hard
reset to the ZIC-8B (similar to a cold boot).
S3, S4, S5 Network Address Switch: Set
the three-digit HNET network address for
the ZIC-8B using the three rotary dial
address switches located near the bottom
of the front panel. (Refer to Figure 1 for the
location of the switches.) The address for
the ZIC-8B must be the same as the
address selected for it in the Zeus Program-
ming Tool. To set the address, turn the
pointers on each of the three dials to the
numbers for the selected address. For
example, if the address is 123, set the
pointer for the HUNDREDS dial to "1" , set
the pointer for the TENS dial to "2" , and set
the pointer for the ONES dial to "3" . The
range of allowable addresses is from 001 to
251 (leading zeros must be used).
The message associated with the ZIC-8B
output circuit in an alternate language.
The device usage of the ZIC-8B signal.
Select usage required from: NAC-Steady,
NAC-Coded, Horn Strobe Sync, Sil Horn
Only (Horn Strobe), Strobe Sync, Strobe
UnSync, 25V Speaker, 70V Speaker, and
100V Speaker.
Determines if Degrade Alarm will activate
the ZIC-8B circuit when asserted.
Determines if the circuit is Silenceable or
Non-Silenceable.
The circuit wiring type must be Class B.
Select actual current load of output
circuit from: 0.0 Amp, 0.5 Amp, 1.0 Amp,
1.5 Amp and 2.0 Amp.
S2
S3
S4
S5
Figure 2
ZIC-8B Switch Location
5
ZIC-2C
RESET
SWITCH
CONNECTORS
TO ZIC-8B
PC BOARD
EXT
POWER
INPUT
POWER
SELECT
BP
S1
POWER
P3
ZIC-8B
1
2
5
6
P4
1
2
5
6
NAC INPUT
NETWORK
SUPERVISION
P5
ADDRESS
ENABLE
1
2
5
6
P6
1
2
5
6
P/N 315-048670-11
96 PIN DIN
PLUG
CONNECTOR