hit counter script

Siemens SITRANS LR560 Operating Instructions Manual page 118

Foundation fieldbus radar level transmitter
Hide thumbs Also See for SITRANS LR560:
Table of Contents

Advertisement

4.2.4. Reminder Activation
Allows you to enable a maintenance reminder.
Options
a) First set the reminder values in Reminder 1 (Required) (4.2.5.)/Reminder 2
(Demanded) (4.2.6.).
b) Select the desired Reminder Activation option.
4.2.5. Reminder 1 (Required)
If Remaining Lifetime (4.2.3.) is equal to or less than this value, the device
generates a Maintenance Required reminder.
Values
a) Modify limit values as required.
b) Set Reminder Activation (4.2.4.) to the desired option.
4.2.6. Reminder 2 (Demanded)
If Remaining Lifetime (4.2.3.) is equal to or less than this value, the device
generates a Maintenance Demanded reminder.
Values
a) Modify limit values as required.
b) Set Reminder Activation (4.2.4.) to the desired option.
4.2.7. Maintenance Status
Indicates which level of maintenance reminder is active.
To display the level of maintenance reminder that is active in AMS Device
Manager see Extended Diagnostics (RESOURCE) on page 72 under
Diagnostics (Resource Block - RESOURCE)
4.2.8. Acknowledge Status
Indicates which level of maintenance reminder has been acknowledged.
Page 112
SITRANS LR560 (FF) – INSTRUCTION MANUAL
REMinder 1 (Maintenance REQuired)
REMinder 2 (Maintenance DEManded)
REMinders 1 AND 2 (Maintenance Required and
Maintenance Demanded)
* OFF
Range: 0 to 20 years
Default: 0.164 years
Range: 0 to 20 years
Default: 0.019 years
.
7ML19985LY01
Device

Advertisement

Table of Contents
loading

Table of Contents