Networkable fire terminal
4.4

Floor repeater display and floor repeater terminal

4.4.1

Floor repeater terminals

FT2010-A1
FT2010-C1
36
Building Technologies
Fire Safety
Floor repeater terminal

Application

Small display and operating panel for floors.
The floor repeater terminal is a C-NET device and can be operated in loops or stub lines.
Features
Display of alarms, pre-alarms, technical messages, faults, isolations possible
Acknowledge and reset events
Event text identical to the fire control panel or fire terminal
Operating access with key
The key switch (Nordic) may be replaced by key switch (Kaba)
Power supply via C-NET, separate 24 V power supply possible

Technical data

Operating voltage
External supply input
Current consumption at 24 V
Quiescent current (LCD lighting inactive)
Maximum current (LCD lighting active)
LCD illumination white
Key switch for operating access
Operating temperature
Storage temperature
Humidity (no condensation permitted)
Communication protocol

Connection terminals

Protection category

Color

Dimensions (W x H x D)

Approvals VdS / LPCB
Floor repeater terminal
Application
Small display and operating panel for floors.
The floor repeater terminal is a C-NET device and can be operated in loops or stub lines.
Features
Display of alarms, pre-alarms, technical messages, faults, isolations possible
Acknowledge and reset events
Event text identical to the fire control panel or fire terminal
Operating access with key
With key switch Kaba and flat rear (sheet metal)
Power supply via C-NET, separate 24 V power supply possible
Technical data
Operating voltage
External supply input
Current consumption at 24 V
Quiescent current (LCD lighting inactive)
Maximum current (LCD lighting active)
LCD illumination white
Key switch for operating access
Operating temperature
Storage temperature
Humidity (no condensation permitted)
Communication protocol
Connection terminals
Protection category
Color
Dimensions (W x H x D)
Approvals VdS / LPCB

Part no.

A5Q00014104
Product data sheet
009393
DC 12...32 V
DC 20...30 V / AC 15...18 V
5 mA
45 mA
6 x 40 characters
Nordic
-8...+42 °C
-20...+60 °C
≤95 % rel.
C-NET
2
0.8...1.5 mm
IP30
grey, ~RAL 7035
283 x 207 x 79 mm
G208011 / 126bp/02
Part no.
S54400-F34-A1
Product data sheet
009393
DC 12...32 V
DC 20...30 V / AC 15...18 V
5 mA
45 mA
6 x 40 characters
Nordic
-8...+42 °C
-20...+60 °C
≤95 % rel.
C-NET
2
0.8...1.5 mm
IP30
grey, ~RAL 7035
283 x 207 x 79 mm
pending / ─