Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
PSU6200 product group are equipped with a proprietary data interface. To a large extent this data interface uses already existing components and infrastructure of power supplies and control systems. This interface is described in detail in the following document. SITOP PSU6200 Diagnostics Interface Application Manual, 04.2019, A5E46632255-1-76...
The last bit of a telegram that has been transferred is immediately followed by the start character of the next telegram. The signal at the receiving input (Digital In) of the higher-level control and evaluation system looks like this: SITOP PSU6200 Diagnostics Interface Application Manual, 04.2019, A5E46632255-1-76...
Page 8
"1" is represented by a rising signal edge. The duration of a bit has a ±5 % tolerance. The high signal level corresponds to 24 V electrical and the low signal level to ground. SITOP PSU6200 Diagnostics Interface Application Manual, 04.2019, A5E46632255-1-76...
"1" if the sum of all of the preceding 1 bits in the telegram is even. Otherwise, the parity bit is "0". The start sequence is not taken into account when gen- erating the parity bit. SITOP PSU6200 Diagnostics Interface Application Manual, 04.2019, A5E46632255-1-76...
Device information Bits 1 - 6 Bits 7 - 13 Bits 14 - 31 Header Status information Temperature and service life Bits 1 - 6 Bits 7 - 13 Bits 14 - 31 SITOP PSU6200 Diagnostics Interface Application Manual, 04.2019, A5E46632255-1-76...
Page 11
1: OK threshold high the front of the device Parallel mode 0 / 1 0: Single mode This bit specifies the position of the DIP 1 at 1: Parallel mode the front of the device SITOP PSU6200 Diagnostics Interface Application Manual, 04.2019, A5E46632255-1-76...
Page 12
Average voltage over the past 3 seconds 24 - 30 Actual output 0.5 A 0 - 63.5 A Represented as unsigned value, MSB is first current transferred Average current over the past 3 seconds Reserved SITOP PSU6200 Diagnostics Interface Application Manual, 04.2019, A5E46632255-1-76...
Page 14
14 001: B of channels 010: C 011: D 100: X 101 - 111: reserved Position 15 0 / 1 0: Y Position 15 of the MLFB information, terminal 1: X type SITOP PSU6200 Diagnostics Interface Application Manual, 04.2019, A5E46632255-1-76...
Page 15
2 ms - 200 ms occurred at the output since previous transfer of the bit 25 - 31 Operating 1000 hours 0 - 127,000 hours in increments of Represented as unsigned value, MSB is first duration 1000 hours transferred SITOP PSU6200 Diagnostics Interface Application Manual, 04.2019, A5E46632255-1-76...
10 prioritization operations, the next telegram of the sequence described above is inserted. SITOP PSU6200 Diagnostics Interface Application Manual, 04.2019, A5E46632255-1-76...