3.1.2.7
Private Measurands, Analog Inputs
3.1.2.8
Private Measurands, Analog Outputs (only transmitted, if an Analog Output module is available)
Power Meter, IEC 60870-5-103, Manual
E50417-B1076-C375-A4, Release 11.2012
Data Unit = 9
Identifier (max. 2 elements)
Cause of Transmission (COT)
Address of ASDU
Function Type = 130
Information Number = 155
Analog Input 1
Analog Input 2
Data Unit = 9
Identifier (max. 2 elements)
Cause of Transmission (COT)
Address of ASDU
Function Type = 130
Information Number = 156
Analog Output Channel 1
Analog Output Channel 2
Note:
Analog Output Channel 1 and Analog Output Channel 2: 0 % = 0 mA; 100 % = 20 mA